12
ANTICIPATION
Function
This allows an anticipated start-up in the morning depending on the outdoor temperature.
Description
This function only works for zone A, and allow the machine to
move from unoccupied zone to zone A earlier if the outdoor
temperature is under a certain value. Use this function to
anticipate the heating start-up during cool days.
This can be adjusted with set point 3221 and 3222.
3221 ! bottom of the slope (°C), Anticipation starting point
3222 ! Slope in Minutes of anticipation per degrees
Example:
Unit with Day A starting at 8.00 am; 3221 set to 3°C and 3222 set to 10 mn/°C;
If the outside temperature is 0°C, then Day A will start at 7.30 a.m.
7h30
8h00
Hour of starting zone A
0°C 3°C
Air Temp. Outside