Table 12. CORE Control System Unit Parameters
Control
Parameter
No
Screen Name
Parameter Short
Description
Control Value
Units Description
Min. Default Max.
133
ZONE SENS
STRTUP DLY
Room Sensor
Start-up Delay
2 2 30 Minutes
Suspends all unit operation room
sensor and Constant Air Volume
with bypass damper applications.
Suspends Fresh Air Heat Control-
Reheat, Fresh Air Cooling Control,
Fresh Air Heat Control options and
all GP outputs.
May be used to stagger unit start-
ups. Does NOT delay demands in
thermostat mode.
134
IAQ INPUT
MODE
Indoor Air Quality
Input Mode
0 1 7 Option
Options are:
0 = Ventilation is disabled.
1 = Demand control ventilation with
outdoor temperature limit and blower
on. (Default)
2 = Demand control ventilation
without Outdoor Temperature Limit
and Blower ON.
3 = Demand control ventilation with
Outdoor Temperature Limit and
Blower AUTO / ON.
4 = Demand control ventilation
without Outdoor temperature Limit
and no blower AUTO / ON.
5 = Outdoor air control with outdoor
temperature limit.
6 = Outdoor air control with outdoor
temperature limit
7 = Building pressure control
System 1 Parameters
137 OCC HEAT STPT
Occupied Heating
Set Point
40
Default may
be altered at
factory test.
95 °F
Backup occupied heating set point.
Used if the communications link
is lost for 5 minutes between the
M3 and NCP. Used only with room
sensor applications.
Set point temperature must be less
than or equal to (Parameter 139
minus Parameter 152).
138
UNOCC HEAT
STPT
Unoccupied
Heating Set Point
40 60 95 °F
Backup unoccupied heating set
point. Used if the communications
link is lost for 5 minutes between the
unit controller and NCP.
Used only in room sensor
applications.
Set point temperature must be less
than or equal to (Parameter 140
minus Parameter 152).
139
OCC COOL
STPT
Occupied Cooling
Set Point
40 75 95 °F
Backup occupied cooling set point.
Used if the communications link is
lost for 5 minutes between the unit
controller and NCP. Used only in
room sensor applications.
Set point temperature must be
greater than or equal to Parameter
137 plus Parameter 152).