eNeRGy-IOM-2020.12-EN
38
CLIMATIC configuration
Settings
1. Supply Air-flow adjustment (depending on customer requirements)
a. 3333 = nominal air flow / pressure
b. 3334 = reduced air flow / pressure
c. 3332 = Manual/Automatic
d. 3331 = Nominal/DeadZone/PartLoad/Pressure
2. Exhaust Air-flow adjustment (optional)
a. 3864 = nominal air flow
b. 3865 = reduced air flow
3. Scheduling (depending on customer requirements)
a. Zones & Modes (Night/Day/Day I/ DayII)
b. Setpoints per mode
4. Regulation temperature probe selection
a. Select the regulation probe (DC, Return, Customer, etc.) in the Room Temp. Config screen
5. Regulation humidity sensor selection (optional)
a. Select the regulation sensor (Remote, Customer) in the Room Hum. Config screen
6. Outside temperature probe selection
a. Select the outdoor temp probe (Unit, Customer) in the Outside Temp. Config screen
7. Outside humidity sensor selection (optional)
a. Select the outdoor hum sensor (Unit, Customer) in the Outside Hum. Config screen
8. Air quality sensor selection (optional)
a. Select the air quality CO2 sensor (Remote, Customer) in the CO2 Config screen
9. Remote display configuration
a. 3151 = DC simple / DC full / DM
10. Minimum fresh air
a. 3121 = minimum opening %
COMMISSIONING