Electrical preheater
WARNING:
electrical pre-heater is connected to main power risk of electrical Shock switch off the
unit prior to open this section
The electrical preheaters are placed before the coil.
Pre-heater is running only with high fresh air rate under low outdoor ambient temperature (see setpoint in control section).
It is protected as standard, against overheat via a high temperature overload protection set at 98°C.
There are three sizes available for each size of unit:
S: Standard heat
M: Medium heat
H: High heat
Unit
Description
Type of modulation
Capacity
Current
E014- E019
Standard
Triac
36 kW
52
A
Medium
Triac
90 kW
129,9 A
High
Triac
108 kW
155,9 A
Unit
Description
Type of modulation
Capacity
Current
E22- E27
Standard
Triac
54 kW
77,9
A
Medium
Triac
108 kW
155,9 A
High
Triac
144 kW
207,8 A
ELECTRICAL PREHEATER