EasyManuals Logo

Lennox eNeRGy Series User Manual

Lennox eNeRGy Series
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #48 background imageLoading...
Page #48 background image
eNeRGy-IOM-2020.12-EN
48
Electrical preheater
WARNING:
electrical pre-heater is connected to main power risk of electrical Shock switch off the
unit prior to open this section
The electrical preheaters are placed before the coil.
Pre-heater is running only with high fresh air rate under low outdoor ambient temperature (see setpoint in control section).
It is protected as standard, against overheat via a high temperature overload protection set at 98°C.
There are three sizes available for each size of unit:
S: Standard heat
M: Medium heat
H: High heat
Unit
Description
Type of modulation
Capacity
Current
E014- E019
Standard
Triac
36 kW
52
A
Medium
Triac
90 kW
129,9 A
High
Triac
108 kW
155,9 A
Unit
Description
Type of modulation
Capacity
Current
E22- E27
Standard
Triac
54 kW
77,9
A
Medium
Triac
108 kW
155,9 A
High
Triac
144 kW
207,8 A
ELECTRICAL PREHEATER
GAS BURNER

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox eNeRGy Series and is the answer not in the manual?

Lennox eNeRGy Series Specifications

General IconGeneral
BrandLennox
ModeleNeRGy Series
CategoryAir Handlers
LanguageEnglish

Related product manuals