Table 63. M3 Control Parameters
Control Parameter
DescriptionUnits
Control Value
No DescriptionUnitsMax.DefaultMin.
Parameter Short
Description
Screen Name
329 BPC PID I CONST
Building Pressure
Control
PID I Constant
0 30 127 Count BPC PID Integral Constant
330 GP A02 MODE
General Purpose A02
Mode
0 0 12
Mode
Selection
1 - Occupied - PID set point A
Unoccupied - PID set point B
2 - Occupied - PID set point A
Unoccupied -Staged output B
3 - Occupied - Staged output A
Unoccupied - PID set point B
4 - Occupied - Staged output A
Unoccupied - Staged output B
5 - Blower On - PID set point A
Blower Off - PID set point B
6 - Blower On - PID set point A
Blower Off - Staged output B
7 - Blower On - Staged output A
Blower Off - PID set point B
8 - Blower On - Staged output A
Blower Off - Staged output B
9 - DI2 on - PID set point B (1)
DI3 on - PID set point A (2)
Otherwise off.
10 - DI2 on - PID set point B (1)
DI3 on - Staged Output A (2)
Otherwise off.
11 - DI2 on - PID set point B (1)
DI3 on - Staged Output A (2)
Otherwise off.
12 - Reserved
(1) -DI3 (on M3) doesn't matter
(2) -DI2 (on M3) is off
331 GP A02 SP A
General Purpose A02
Set Point A
0 0 100 %
Analog output channel 2, set
point A.
332 GP A02 SP B
General Purpose A02
Set Point B
0 0 100 %
Analog output channel 2, set
point B.
333 GP A02 STG A
General Purpose A02
Stage A
0 0 100 %
Analog output channel 2, stage
A
334 GP A02 STG B
General Purpose A02
Stage B
0 0 100 %
Analog output channel 2, stage
B
335 GP A02 OUTPUT
General Purpose A02
Output
0 0 1 Selection
0 = PWM
1 = 0-10 VDC
336 GP A02 PWM FREQ
General Purpose A02
Pulse-Width Modulation
Frequency
50 200 2000 Hz Analog output PWM frequency.
337 GP A02 KP
General Purpose A02
Proportional Constant for
PID
0 0 100 Count
Analog output channel 2 PID
loop proportional constant.
338 GP A02 KI
General Purpose A02
Integral Constant for PID
0 0 100 Count
Analog output channel 2 PID
loop integral constant.
340 GP A02 MIN OUPUT
General Purpose A02
Minimum Output
0 0 100 %
Analog output channel 2 mini
mum output.
341 GP A02 MAX OUPUT
General Purpose A02
Maximum Output
0 100 100 %
Analog output channel 2 maxi
mum output.