Table 63. M3 Control Parameters
Control Parameter
DescriptionUnits
Control Value
No DescriptionUnitsMax.DefaultMin.
Parameter Short
Description
Screen Name
342 GP A02 SOURCE
General Purpose A02
Source
1 1 3
SOURCE
SELECTION
Source/feedback for the PID
loop.
1 = Analog input 1 on GP3 A02
2 = Analog input 2 on GP3 A02
3 = Analog input 3 on GP3 A02
343 GP A02 CYCL INTRVL
General Purpose A02
Cycle Interval
0 1 180 Sec
Frequency of execution of PID
loop.
344 GP A03 MODE
General Purpose A03
Mode
0 0 11
Mode
Selection
1 - Occupied - PID set point A
Unoccupied - PID set point B
2 - Occupied - PID set point A
Unoccupied -Staged output B
3 - Occupied - Staged output A
Unoccupied - PID set point B
4 - Occupied - Staged output A
Unoccupied - Staged output B
5 - Blower On - PID set point A
Blower Off - PID set point B
6 - Blower On - PID set point A
Blower Off - Staged output B
7 - Blower On - Staged output A
Blower Off - PID set point B
8 - Blower On - Staged output A
Blower Off - Staged output B
9 - DI2 on - PID set point B (1)
DI3 on - PID set point A (2)
Otherwise off.
10 - DI2 on - PID set point B (1)
DI3 on - Staged Output A (2)
Otherwise off.
11 - DI2 on - PID set point B (1)
DI3 on - Staged Output A (2)
Otherwise off.
12 - Reserved
(1) -DI3 (on M3) doesn't matter
(2) -DI2 (on M3) is off
(1) -DI3 (on M3) doesn't matter
(2) -DI2 (on M3) is off
345 GP A03 SP A
General Purpose A03
Set Point A
0 0 100 %
Analog output channel 3, set
point A.
346 GP A03 SP B
General Purpose A03
Set Point B
0 0 100 %
Analog output channel 3, set
point B.
347 GP A03 STG A
General Purpose A03
Stage A
0 0 100 %
Analog output channel 3, stage
A
348 GP A03 STG B
General Purpose A02
Stage B
0 0 100 %
Analog output channel 3, stage
B
349 GP A03 OUTPUT
General Purpose A03
Output
0 0 1 Selection
0 = PWM
1 = 0-10 VDC
350 GP A03 PWM FREQ
General Purpose A03
Pulse-Width Modulation
Frequency
50 200 2000 Hz
Frequency of execution of PID
loop.
351 GP A03 KP
General Purpose A03
Proportional Constant
0 0 100 Count
Analog output channel 3 PID
loop proportional constant.
352 GP A03 KI
General Purpose A03
Integral Constant
0 0 100 Count
Analog output channel 3 PID
loop integral constant.
354 GP A03 MIN OUPUT
General Purpose A03
Minimum Output
0 0 100 %
Analog output channel 3 mini
mum output.
355 GP A03 MAX OUPUT
General Purpose A03
Maximum Output
0 100 100 %
Analog output channel 3 Maxi
mum output.