Table 1. Server Specifications (continued)
Specification
Description
Environment
Air temperature:
Server on: to 45°C (41° to 113°F); altitude: 0 to 3050 m (10,006 ft) derate
maximum dry bulb temperature 1°C (33°F) per 125 m (410 ft) above 950 m
(3,117 ft). Maximum rate of change 20°C (68°F) per hour
Server off: to 45°C (41° to 113°F)
Shipment: -40°C to 60°C (-40°F to 140°F)
Humidity range (noncondensing):
Server on: Minimum = higher (more moisture) of -12°C (10°F) dew point and 8%
to 90% relative humidity; maximum dew point: 24°C (75°F)
Server off: 8% to 90% relative humidity; maximum dew point: 27°C (80°F)
Shipment: 5% to 100%
Notes:
Particulate contamination
Attention: Airborne particulates and reactive gases acting alone or in
combination with other environmental factors such as humidity or temperature
might pose a risk to the server. For information about the limits for particulates and
gases, see “Particulate contamination” in ThinkSystem SR950 Maintenance
Manual.
ASHRAE compliance information (see the “Operating Environment” section of
the
ThinkSystem SR950 Product Guide at http://lenovopress.com/LP0647
for specific
ASHRAE compliance levels for each server configuration):
The server is designed for thermal compliance in ASHRAE A4 ambient
environments. Certain processor and adapter configurations will limit product
environmental support to ASHRAE A2 ambient conditions.
If 82xx processors are installed, 60 mm x 38mm, 19K internal hot-swap fans
(01PG490) must also be installed to meet CPU cooling requirements at 35°C.
205W processors used in an eight-socket configuration might experience a
slight drop in performance under extreme workloads when the ambient
temperature is above 30°C.
NVMe devices are supported up to an ambient temperature of 35°C.
Operating systems
Supported and certified operating systems:
Microsoft Windows Server
VMware ESXi
Red Hat Enterprise Linux
SUSE Linux Enterprise Server
References:
Complete list of available operating systems:
https://lenovopress.com/osig.
OS deployment instructions: “Deploy the operating system” on page 266.
Particulate contamination
Attention: Airborne particulates (including metal flakes or particles) and reactive gases acting alone or in
combination with other environmental factors such as humidity or temperature might pose a risk to the
device that is described in this document.
Chapter 1. Introduction 9