EasyManua.ls Logo

Lenze 8104 - 4 Inverter Connections; Mains and Motor Connection; Mains Choke

Lenze 8104
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical description 8100_ A
11
4. INVERTERCONNECTIONS
4.1 MAINS AND MOTOR CONNECTION
M
3""
"'---"
Three - phase motor
3""'6
*'
Filter
.
L1 N PE
Operation without brake chopper
The PE connection can, in addition to the power plug, be bolted to the right terminal
clamp at the front side of the inverter.
8106_ A inverters must only be operated with the correct mains choke.
The power plug may only be connected or disconnected when the device is without
voltage.
*) For screenings see 3.1
Screened cables and mains filters are necessary for radio interference
suppression to EN 55011, class A or B (see 3.2).
4.1.1 MAINSCHOKE
Advantages when using a mains choke:
Compliance with surge strength dass I according to VDE 0160
Reduction of mains feedback
Increasing the inverter life
Reduction of radio interference
Mains chokes are not supplied with the inverter.