Technical description 8100_ A
39
7.2.14
PRESELECTION OF JOG REFERENCEC038
REFERENCE39
The JOG frequency set-va lues are set using the codes C038 and C039. First, enter
the JOG set-value under C038. This JOG set-value can be assigned a frequency
under C039. If e.g. -2- has been selected under C038, you can enter the frequency
for JOG 2 under C039.
JOG set-values which are larger than fdmax are limited internally to fdmax'
To activate the JOG set-values see 7.3.5. For activated JOG set-value, set-value 2 is
switched
off.
7.3 CONTROL PARAMETERS
t
I
Depending on the operating mode C001 (see 7.1.2). the control parameters are
changed via the control terminals, the operating unit 810288 or via the LECOM
interface.Forterminalcontrol, the followingcodes serve as displays. If keypad or
LECOMcontrol is selected, the codes serve as operating parameters.
7.3.1 CONTROLLER ENABLE C040
Controller enable
Independently of the operating mode C001, the controller must be enabled by
applyinga voltage between 13 and 30 V across terminal28. When using the
operating unit 810288, the controller can always be inhibited using the STP key and
be enabled by pressing SH + STP.
In the operating mode
LECOM operation (C001 = -3-). the controller can be inhibited
and enabled additionally using
C040 = -1- (via the LECOM interface)
The controller can only be enabled via those input channels, which were used to
inhibit the controller:
o
- Terminal 28
-Code C040 (inthe operating modes keypad and LECOMoperation)
- Stop key
-Trip fault indication
If, for example, the controller has been inhibited
in LECOM operation via C040 = -0-,
it can only be enabled via C040 = -1-.
Controller enable after mains connection
The controller is enabled after mains connection,
if a voltage of 13 ... 30 V is applied
across terminal 28.
Only in the operating mode C001 = -3-, the controller must be
enabled. in addition
via LECOM interface (C040 = -1-).