4 Technicaldescription8100_A
2 TECHNICAL DATA
2.1 INVERTERDATA
Lenze
Inverter type
8101 8102 8103 8104 8105
8106
Output power
SN/kVA
0.76 1.0 1.3
1.5 2.7 3.6
Rated motor power
PN/W
250 370 550
750
1500 2200
(4-po1e)
Mains voltage
Vmains
190...260V
tO% 50. ..60Hz
Rated mains current
Imains/A
4.5
5.0 7.0 9.0
15 17
Output voltage
V
3 x 0
... Vmains
Rated output current
IN/A
2.0 2.6 3.4 4.0 7.0 9.5
Max. inverter current
Imax/A
without Clamp
3.2 4.2 5.4 6.4
11.
2 15.
2
with Clamp
2.4 3.1
4.1
4.8 8. 4 11. 4
Power loss
pv/W
25
35
50
70 90 150
fd = 50Hz,
I=IN
Output frequency
fd
o. . .t4 80Hz
Master voltage
UL
0.. .10V or -10V...+10V
Master current
IL
0...20mA
or -20mA.. .+2 OmA
4...20mA
or t 4mA.. .t20mA
Ambient temperature
Tu
o to 45°C
Enclosure IP20 to DIN 40050
Part no. 356 845 356 846
356 848 356 850 356 851 356 852