Commissioning
821XKlimaBA0399 5-17
Code settings - unit 2:
Code Name Possible settings
C
o
d
e
N
a
m
e
Lenze Selection
C001 Operating mode -0- -0- Setpoint selection via term. 8. Control via terminals.
Parameter setting via 8201BB
C005 Configuration -0- -0- Operation with open-loop control via terminal 8
C014 Operating mode -0- -3- Square characteristic V
f
d
2
with constant V
min
boost
According to the information given in both tables (code setting for unit 1 and 2):
1. All other parameters are based on the factory setting.
2. Set the rated motor data (depends on the motor used) under C088 (rated motor current) and C091 (motor cos