Configuration
7-4 821XKlimaBA0399
Code IMPORTANTPossible settingsNameCode IMPORTANT
InfoSelectionLenze
Name
C005
¤
Configuration -0- -0- Operation with open-loop control via
terminal 8
-1- Operation with open-loop control via
terminal 8 with setpoint summation via
frequency input E1
-2- Operation with open-loop control via
frequency input E1 with setpoint summation
via terminal 8
-3- Operation with open-loop control via
frequency input E1 with torque limitation via
terminal 8
-4- Torque selection via terminal 8 with speed
limitation via f f
dmax
(C011)
-5- Torque selection via terminal 8 with speed
limitation via frequency input E1
-6- Operation with closed-loop control; setpoint
via terminal 8 with digital frequency
feedback via terminal E1
-7- Operation with closed-loop control, setpoint
via frequency input E1 with analog
feedback via terminal 8
Selections -4-
and -5- are only
permitted for
motor-current
control
(C014 = 4)and
with activated
flying restart
circuit
(C1 42 = 2. 3).
C007
¤
Te rmi na l
configuration
-0- E4 E3 E2 E1
-0- CW/CCW DC brake JOG1/2/3
-1- CW/CCW PAR JOG1/2/3
-2- CW/CCW QSP JOG1/2/3
-3- CW/CCW PAR DC brake JOG1
-4- CW/CCW QSP PAR JOG1
-5- CW/CCW DC brake Trip set JOG1
-6- CW/CCW PAR Trip set JOG1
-7- CW/CCW PAR DC brake Trip set
-8- CW/CCW QSP PAR Trip set
-9- CW/CCW QSP Trip set JOG1
-10- CW/CCW Trip set UP DOWN
-
CW=
CWrotation
-
CCW=
CCWrotation
-
DC brake =
DC injection
brake
-
PAR =
Change of
parameter sets
-
JOG=
JOG frequency
-
QSP =
Quick stop