Configuration
7-6 821XKlimaBA0399
Code IMPORTANTPossible settingsNameCode IMPORTANT
InfoSelectionLenze
Name
C008
¤
Function relay K1 -1- -0- Readyforoperation
-1- TRIP fault message
-2- Motor is running
-3- Motor is running / CW rotation
-4- Motor is running / CCW rotation
-5- Field frequency f
d
=0
-6- f
dset
reached
-7- Q
min
reached
-8- I
max
reached
-9- Overtemperature (
J
max
-10
C)
-10- TRIP or Q
min
or IMP
822X/824X -11- PTC warning
-12- Apparent motor current (C054)< threshold
C156
-13- Apparent motor current (C054)< threshold
C156 and f
d
>Q
min
threshold (C017)
-14- Apparent motor current (C054)< threshold
C156 and input of ramp function generator
= output of ramp function generator
822X/824X -15- Warning motor phase failure
-16- f
d
(C050)< f
dmin
(C010)
C009* Device address 1 1 {1} 99 Only for LECOM
applications
C010 Minimum field
frequency
0.00 0.00 {0.02Hz} 480.00
C011 Maximum field
frequency
50.00 7.50 {0.02Hz} 480.00
C012 Acceleration time 5.00 0.00 {0.02s} 1300.00
C013 Deceleration time 5.00 0.00 {0.02s} 1300.00
C014
¤
Operating mode
-2- Linearcharacteristic V
f
d
with constant
V
min
boost
-
3
-
S
a
r
e
c
a
r
a
c
t
e
r
i
s
t
i
c
V
f
2
w
i
t
c
o
s
t
a
t
V
m
i
n
o
o
s
t
-3- Square characteristic V
f
d
2
with constant
V
min
boost
-4- -4- Motor-current control
C015 V/f rated
frequency
50.00 7.50 {0.02Hz} 960.00
C016 V
min
setting 0.00 0.00 {0.2 %} 40.0 depends of the
unit
C017 Threshold Q
min
0.00 0.00 {0.02Hz} 480.00