Troubleshooting and fault elimination
Error elimination
Controller in clamp operation
3
32
EDKVF93−05 EN 1.0
Adjustment
U
DC
t C0912³
t < C0912
t = C0912
01
IMP
9300vec142
Fig.3−2 Influence of the delay time (C0912)
Switch−off threshold OU
Switch−on threshold OU
The period of time between exceeding the switch−off threshold OU and undershooting the
switch−on threshold OU equals or is higher than the delay time set in C0912.
After undershooting the switch−on threshold OU, the pulse inhibit is deactivated.
The period of time between exceeding the switch−off threshold OU and undershooting the
switch−on threshold OU is lower than the delay time set in C0912.
The pulse inhibit is deactivated after the delay time in C0912 has elapsed.
ƒ In C0912 the delay time is set in [ms].The Lenze setting can be changed by the factor
0.5 ... 2.