Address Name / seng range / [default seng] Informaon
0x2012:005 Device informaon: SD card free memory
Read only
Display of the currently free memory on the SD card in kilobytes.
0x2012:006 Device informaon: SD card used memory
Read only
Display of the currently occupied memory on the SD card in kilobytes.
0x2013:001 Applicaon informaon: Acve applicaon
Read only
Display of the acve applicaon.
100 "User" technology applicaon
0x2013:002 Applicaon informaon: Applicaon Credit required
Read only
Display of the applicaon credit required for the loaded applicaon.
0x2539:002 Hardware-Diagnose: Control board temperature
Read only: x.x °C
Interior temperature of the device.
0x2539:003 Hardware-Diagnose: CPU temperature
Read only: x.x °C
Processor temperature of the device.
0x2D85:001 Fan diagnoscs: Status
Read only
Fan status in %
0% = Fan o
30%...100% = Speed in %
0x2D85:002 Fan diagnoscs: Speed
Read only
Speed in rpm.
0x5810:001 Applicaon diagnoscs: Applicaon state
Read only
Display of the applicaon status.
0 Unknown/applicaon missing
1 Running
2 Stopped
3 Stopped at breakpoint
0x5810:002 Applicaon diagnoscs: Used memory size
Read only
Display of the memory used by the applicaon in kilobytes.
12.3.2 Network diagnoscs
The current status of the inserted extension module is represented via the following
parameters. 0xC231F
If the network module is added at a later date, it must match the controller
used.
Several parameters are available for the seng and funcon of the PROFINET as extension
module. 4PROFINET ^ 70
Parameter
Address Name / seng range / [default seng] Informaon
0x231F:001 Communicaon module ID: Acve module ID
Read only
Display of the network opons currently congured in the device.
Note!
When switched on, the device checks whether the parameter sengs
saved in the memory module match the device hardware and rmware.
In case of an incompability, a corresponding is error message is output.
48 No network
65 AS-Interface
67 CANopen
71 EtherNet/IP
72 BACnet
78 POWERLINK
80 PROFIBUS
82 PROFINET The controller currently supports these network opons.
84 EtherCAT
86 Modbus TCP/IP
87 Modbus
Diagnoscs and fault eliminaon
Diagnosc parameters
Network diagnoscs