11 Upgrade/downgrade of the controller
The controller rmware to be installed can be obtained via the »Package Manager«.
Precondions with engineering PC:
Lenze »Package Manager«
Installed Lenze »Firmware loader«
USB ash drive with at least 200 MB free memory
The rmware package to be installed via the »Package-Manager« is selected via the
Lenze »Firmware loader«. The selected rmware is then copied to the USB ash drive inserted
in the engineering PC.
How to install the rmware:
1. Insert the prepared USB ash drive into USB port 1 X61 or USB port 2 X62 on the controller.
2. Restart the controller by line voltage switching.
When starng up with an inserted USB ash drive, the rmware is transferred to the device
and installed. The controller then restarts automacally.
Aer the rmware has been updated successfully, the USB ash drive can be removed.
The rmware on the USB ash drive is stored in the controller as well as on the
inserted SD card. 4Replace controller ^ 83
LED status display
"STA" LED (yellow/green) Meaning
Update/Downgrade process is running.
Update/Downgrade process is carried out.
The rmware update can be detected by the status LEDs of the controller. Details on the
update are entered in the logbook.
Upgrade/downgrade of the controller
85