6.6.3 Restart device
When the Restart device command is executed, the network connecon is lost.
If the network seng was not changed, the device can be accessed again aer
approx. 60 seconds.
Parameter
Address Name / seng range / [default seng] Informaon
0x2022:035 Device commands: Restart Device
When the device command has been executed successfully, the value
0 is shown.
Do not switch o the supply voltage while the device command is
executed and do not unplug the memory module from the controller!
0 O/Ready Only status feedback
1 On/Start Restart of the device.
2 In progress Only status feedback
3 Acon cancelled
4 No access
5 No access (Inverter disabled)
6.6.4 Start/stop applicaon
Applicaon credit may be required to execute the PLC applicaon.
When the applicaon is compiled, the required applicaon credit is determined.
The value is entered in the following parameters. 40x2013:002
Insucient applicaon credit results in the applicaon being executed with a
delay. Please contact your Lenze service center if you require addional
applicaon credit.
The PLC applicaon is controlled using the following device commands:
Parameter
Address Name / seng range / [default seng] Informaon
0x2022:044 Device commands: Start applicaon
When the device command has been executed successfully, the value
0 is shown.
Do not switch o the supply voltage while the device command is
executed and do not unplug the memory module from the controller!
0 O/Ready Only status feedback
1 On/Start The loaded PLC applicaon is started.
2 In progress Only status feedback
3 Acon cancelled
4 No access
5 No access
0x2022:045 Device commands: Stop applicaon
When the device command has been executed successfully, the value
0 is shown.
Do not switch o the supply voltage while the device command is
executed and do not unplug the memory module from the controller!
0 O/Ready Only status feedback
1 On/Start The running PLC applicaon is stopped.
2 In progress Only status feedback
3 Acon cancelled
4 No access
5 No access
Device sengs
Device commands
Restart device
31