Technical data
Terminal description
Supply modules
4
l
48
EDS700ACBA EN 5.1
Mains connection
X100 Labelling Description
PE Protective earth +
L1
Mains phases 3 PE / AC 400/480 V
L2
L3
i700P003
Terminal data
Conductor cross−section Tightening torque
!
[mm
2
] [AWG] [Nm] [lb−in]
flexible 0.5 ... 16 22 ... 6 1.2 ... 1.5 10.6 ... 13.3 5.5 x 1
X100 Electrical data
L1
L2
L3
PE
Rated voltage 400/480 V
Voltage range 320 ... 528 V
PE
L3
L2
L1
+
+
3 PE /AC
X100
PE
L3
L2
L1
+UG -UG
i700S010 7
Fig. 3 Wiring of X100
X100 Mains voltage connection of power supply module
L1, L2, L3 Mains phases 3 / AC
PE PE conductor, +
UG (+, −) DC bus