Commissioning
The most important codes for commissioning
T
EDK82MV222 DE/EN/FR 9.0
NOP
L
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0007
uSEr
Fixed
configuration
of digital
inputs
Change under C0007 will
be copied to the
corresponding subcode of
C0410. Free configuration
under C0410 sets C0007 =
255!
0
E4 E3 E2 E1
z CW/CCW = CW
rotation/CCW rotation
z DCB = DC-injection brake
z QSP = Quick stop
z PAR = Parameter set
changeover (PAR1
Ù
PAR2)
–PAR1=LOW,PAR2=
HIGH
The terminal must be
assigned to the function
”PAR” in PAR1 and
PAR2.
Configurations with
”PAR” are only allowed
if C0988 = 0
z TRIP set = external fault
0
CW/CC
W
DCB JOG2/3 JOG1/3
1
CW/CC
W
PAR JOG2/3 JOG1/3
2
CW/CC
W
QSP JOG2/3 JOG1/3
3
CW/CC
W
PAR DCB JOG1/3
4
CW/CC
W
QSP PAR JOG1/3
5
CW/CC
W
DCB TRIP set JOG1/3
j6
CW/CC
W
PAR TRIP set JOG1/3
7
CW/CC
W
PAR DCB TRIP set
8
CW/CC
W
QSP PAR TRIP set
9
CW/CC
W
QSP TRIP set JOG1/3
10
CW/CC
W
TRIP set UP DOWN
C0007
uSEr
(cont.)
E4 E3 E2 E1
z Selection of
fixed
setpoints
JOG1/3 JOG2/3
LOW LOW
HIGH LOW
LOW HIGH
HIGH HIGH
active
C0046
JOG1
JOG2
JOG3
11
CW/CC
W
DCB UP DOWN
12
CW/CC
W
PAR UP DOWN
13
CW/CC
W
QSP UP DOWN
14
CCW/QS
P
CW/QSP DCB JOG1/3
15
CCW/QS
P
CW/QSP PAR JOG1/3
16
CCW/QS
P
CW/QSP JOG2/3 JOG1/3
17
CCW/QS
P
CW/QSP PAR DCB
18
CCW/QS
P
CW/QSP PAR TRIP set
19
CCW/QS
P
CW/QSP DCB TRIP set