Commissioning
The most important codes for commissioning
EDK82MV222 DE/EN/FR 9.0
L
NOO
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0002*
uSEr
(cont.)
Saving of own
settings
9
PAR1 Ö Own settings
You can save your own basic
settings for a controller (e.g.
machine delivery status):
1. Ensure that parameter set
1isactive
2. Controller inhibit
3. Set C0003 = 3,
acknowledge with 
4. Set C0002 = 9,
acknowledge with ,to
save your own basic
settings
5. Set C0003 = 1,
acknowledge with 
6. Enable the controller.
C0002*
uSEr
(cont.)
Loading/copyi
ng of your
own basic
settings
Using this function, PAR1 can
be copied to parameter sets
PAR2 ... PAR4
5
Own settings Ö PAR1
Restorage of own basic
setting in the selected
parameter set
6
Own settings Ö PAR2
7
Own settings Ö PAR3
8
Own settings Ö PAR4
C0003*
Non-volatile
parameter
saving
1
0 ParameternotsavedinEEPROM Data loss after mains
disconnection
1 Parameter always saved in
EEPROM
z Active after every mains
connection
z Cyclic parameter changes
via bus module are not
allowed.
3 Own settings saved in EEPROM Subsequently save parameter
set 1 as own basic setting
with C0002 = 9