Electrical installation
Power terminals
5
96
EDKCSEX064 DE/EN/FR 6.0
5.2 Power terminals
ECSXA080
Fig. 5−1 Plug connectors for power terminals
Danger!
Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ Death or severe injuries when the device is touched in the event
of a fault.
Protective measures:
ƒ Implement the actions required in the EN 61800−5−1. Especially:
Fixed installation
PE connection must conform to standards (PE conductor
diameter ³ 10 mm
2
or PE conductor must be connected twice)