Electrical installation
Power terminals
5
54
EDBCSXS064 EN 4.0
Shielded cables
The following factors decisively determine the effect of the shielded cables:
ƒ Good shield connection
Ensure a contact surface as large as possible
ƒ Low shield resistance
Only use shields with tin−plated or nickel−plated copper braids (shields with steel
braids cannot be used).
ƒ High overlap rate of the braid
At least 70 ... 80 % with 90° overlap angle
The ECSZS000X0B shield mounting kit includes a wire clamp and shield sheet.