Commissioning
Code table
7
l
66
EDBMZ9374X DE/EN/FR 4.2
7.5 Code table
How to read the code table
Column Abbreviation Meaning
Code
Cxxxx Code Cxxxx
Parameter value accepted immediately
(ONLINE)
1 Subcode 1 of Cxxxx
2 Subcode 2 of Cxxxx
[Cxxxx] Changed parameter of the code is accepted by switching off the power
supply for the terminal extension
Name Name of the code
Lenze Lenze setting (default value)
à
Further information can be obtained from "IMPORTANT"
Selection 1
{%}
99 Min. value {unit} Max. value
IMPORTANT Brief, important explanations
Code Possible settings
IMPORTANT
No. Name Lenze Selection
[C0010] I/O reversal 0
Bit 0 ... bit 7
Bit 8 ... bit 15
Bit 16 ... bit 23
Bit 24 ... bit 31
Inputs/Outputs 9374 master
Inputs/Outputs 9374 slave1
Inputs/Outputs 9374 slave2
Inputs/Outputs 9374 slave3
32 bit information
Configuration of the
digital inputs/outputs
Bit value 0
Bit value 1
Input
Output
C0011
Debouncing
time
1 1 {1 msec} 255 Delay for the data
acceptance at the digital
inputs
C0012 Switching off
event
transmission
1
Bit 0 ... bit 7
Bit 8 ... bit 15
Bit 16 ... bit 23
Bit 24 ... bit 31
Inputs/Outputs 9374 master
Inputs/Outputs 9374 slave1
Inputs/Outputs 9374 slave2
Inputs/Outputs 9374 slave3
Bit value 0
Bit value 1
Cyclic transmission
Event−triggered transmission
C0014
Higher−level
transmission
cycle
100 100 {1 msec} 65000 Independent of the
setting in C0015
C0015 Minimum
transmission
break
0
0 {1 msec} 255
Effective only with
event−triggered process
data transmission.
Long transmission breaks
reduce the bus load.
0 = no transmission break
C0030 Monitoring
output
terminals
0
0 {100 ms} 25500
If a communication error
has occurred and the
monitoring time has
elapsed, the digital
outputs change to LOW
level.
0 = no monitoring