11Operang Instrucons i410-Cabinet
Electrical installaon
5.5 Single-phasemainsconnecon230/240V
Terminaldata,1-phase230/240V
I41AExxxB I41AExxxB I41AxxxB I41AExxxB
Inverter [kW] 0.25 ... 0.75 1.5 ... 2.2 0.25 ... 2.2 0.25 ... 2.2
Connecon Mains connecon
X100
PE connecon
Motor connec-
on X105
Connecon type Pluggable screw terminal PE screw
Pluggable screw
terminal
Max. cable cross-secon mm² 2.5 6 6 2.5
Stripping length mm 8 10 8
Tightening torque Nm 0.5 0.7 2 0.5
Tools required 0.5 x 3.0 0.6 x 3.5 Torx 20 0.5 x 3.0
Fusing data
Inverter [kW] 0.25 0.37 0.75 1.5 2.2
Rated motor current A 1.7 2.4 4.2 7 9.6
Max. current [15 s] A 2.6 3.6 6.3 10.5 14.4
Operaonwithoutmainschoke
Fuse
Characterisc gG/gL or gRL
Max. rated current A 10 10 16 25 25
Circuit breaker
Characterisc B
Max. rated current A 10 10 16 25 25
Earth-leakage circuit breaker
1-phase mains connecon ≥ 30 mA, type B
Mainsconnecon
Valid for I41AExxxB inverter.
1/N/PE
AC 170 V ... 264 V
45 Hz ... 65 Hz
F1
Q1
X100
L1
L2/N
PE
N
L3
L2
3/N/PE
AC 208 ... 240 V
Valid for I41AExxxB inverter.
F1
…
F2
Q1
X100
L1
L2/N
2/PE
AC 170 V ...
45 Hz ... 65 Hz
PE
N
L2
2/N/PE
AC 208 V ...
Motorconnecon
X105
U
V
W
Rb1
Rb2
M
3~