Inial switch-on
Operang Instrucons i410-Cabinet
7 Commissioning
DANGER
Electrical voltage
Incorrect wiring can cause unexpected states during the commissioning phase.
Wiring must be complete and correct.
Wiring must be free of short circuits and earth faults.
The motor circuit conguraon (star/delta) must be adapted to the inverter.
The motor must be connected in-phase (rotang direcon).
The "emergency o" funcon of the overall system must operate correctly.
Clear hazardous area.
Observe safety instrucons and safety clearances.
6 Inialswitch-on
DANGER
Electrical voltage
Incorrect wiring can cause unexpected states during the commissioning phase.
Wiring must be complete and correct.
Wiring must be free of short circuits and earth faults.
The motor circuit conguraon (star/delta) must be adapted to the inverter.
The motor must be connected in-phase (rotang direcon).
The "emergency o" funcon of the overall system must operate correctly.
Clear hazardous area.
Observe safety instrucons and safety clearances.
Condions
The power connecons must be wired.
The digital inputs X3/DI1 (start/stop), X3/DI3 (reversal of rotaon direcon) and
X3/DI4 (frequency preset 20 Hz) must be wired.
The analog input X3/AI1 must not be wired or connected to GND.
Switch on mains voltage
Switch on mains voltage and check readiness for operaon.
Observe LED status displays “RDY” and “ERR” on the inverter front panel.
See “LED status”.