7
Technical data
Operang Instrucons i410-Cabinet
3 Technical data
3.1 Standardsandoperangcondions
Conformies CE 2014/35/EU, 2014/30/EU
EAC TR CU 004/2011, TR CU 020/2011
RoHS 2 2011/65/EU
Approvals
C
UL
US
UL 61800-5-1, CSA 22.2 No. 274
Energyeciency Class IE2 EN 50598-2
Protecontype IP20 EN 60529 (except in wire range of terminals)
NEMA 250 (type 1 protecon against accidental
contact only)
Open type Only in UL-approved systems
Power systems TT, TN Voltage against earth: max. 300 V
IT Apply the measures described for IT systems!
Mains switching 3 x within one minute possible
Operaonwithearth-leakagecircuit
breaker
(oponal)
(230-Vmainssupply)
30 mA
Cable length for EMC Category C2 Max. 20 m (≤0.37 kW max. 5 m)
Category C3 Max. 35 m (≤0.37 kW max. 15 m)
Switching frequencies 2, 4, 8, 16 kHz. The rated output currents apply at
45 °C and switching frequencies of 2 and 4 kHz, and at
40 °C and switching frequencies of 8 and 16 kHz
Ambient temperature 55 °C (derang of 2.5 %/ °C above 45 °C)
Max. output frequency 0 Hz ... 599 Hz
Overload capacity
(230/240Vmainssupply)
200 % for 3s; 150 % for 60 s
3.2 ConnecontotheITsystem
NOTE
Electrical voltage
Internal components have ground potenal if the IT screws are not removed.
The monitoring devices of the IT system will be triggered.
Before connecon to an IT system be absolutely sure to remove the IT screws.
TX10
TX10