Commissioning
Operang Instrucons i410-Cabinet
Display code Name
Possiblesengs/
value ranges
Keypad code Informaon
P400.02 Run Digital input 1 [11] Assignment of a trigger to the “Run” funcon.
Funcon1:Start/stopmotor(defaultseng)
Funcon 1 is acve if no further start commands (start forward/start reverse) have been connected to triggers, no keypad control is acve and no
network control is acve.
Trigger = TRUE: Let motor rotate forward (CW).
Trigger = FALSE: Stop motor according to stop funcon (P203.03).
Funcon2:Startclearance/stopmotor
Funcon 2 is acve if further start commands have been connected to triggers, the keypad control is acve or the network control is acve.
Trigger = TRUE: Start commands of the acve control source are enabled.
Trigger = FALSE: Stop motor.
P400.03 Quick stop Not connected [0] Assignment of a trigger to the “Acvate quick stop” funcon.
Trigger = TRUE: Acvate quick stop. Quick stop ramp P225.00.
Trigger = FALSE: Deacvate quick stop
P400.04 Error reset Digital input 2 [12] Assignment of a trigger to the “Reset error” funcon.
Trigger = FALSE > TRUE (edge): The acve error is reset (acknowledged) if the error condion is no longer acve and the error is reseable.
Trigger = FALSE: No acon.
P400.05 DC braking Not connected [0] Assignment of a trigger to the “Acvate DC braking” funcon.
Trigger = TRUE: Acvate DC braking.
Trigger = FALSE: Deacvate DC braking.
P400.06 Start forward Not connected [0] Assignment of a trigger to the “Start forward (CW)” funcon.
Trigger = FALSE > TRUE (edge): Let motor rotate forward.
Trigger = TRUE > FALSE (edge): No acon.
Stop via P400.01 (default seng of digital input 1).
P400.07 Start reverse Not connected [0] Assignment of a trigger to the “Start reverse (CCW)” funcon.
Trigger = FALSE > TRUE (edge): Let motor rotate backward.
Trigger = TRUE > FALSE (edge): No acon.
Stop via P400.01 (default seng of digital input 1).
P400.08 Run forward Not connected [0] Assignment of a trigger to the “Run forward (CW)” funcon.
Trigger = TRUE: Let motor rotate forward.
Trigger = FALSE: Stop motor.
Stop via P400.01 (default seng of digital input 1).
P400.09 Run reverse Not connected [0] Assignment of a trigger to the “Run reverse (CCW)” funcon.
Trigger = TRUE: Let motor rotate backward.
Trigger = FALSE: Stop motor.
Stop via P400.01 (default seng of digital input 1).
P400.13 Reverse rot. dir. Digital input 3 [13] Assignment of a trigger to the “Reverse rotang direcon” funcon.
Trigger = TRUE: The setpoint specied is inverted (i.e. the sign is inverted).
Trigger = FALSE: No acon / deacvate funcon again.
P400.18 Setp: Preset B0 Digital input 4 [14] Assignment of a trigger to the “Acvate preset (bit 0)” funcon.
Bit with the value 2
0
for the bit-coded selecon and acvaon of a congured setpoint (preset value).
Trigger = FALSE: Bit = “0”.
Trigger = TRUE: Bit = “1”.
Defaultseng=boldprint|*Defaultsengisdevice-dependent