3 Technical data
3.1 General data and operating conditions
Conformity and approval
Conformity
CE
2014/35/EU Low−Voltage Directive
2014/30/EU EMC Directive
EAC
TP TC 004/2011
(TR ZU 004/2011)
Regarding the safety of
low−voltage equipment
Eurasian conformity
TR ZU: Technical regulation of the tariff union
TP TC 020/2011
(TR ZU 020/2011)
Electromagnetic
compatibility of technical
products
Approval
UL/CSA
UL 61800−5−1
Industrial Control Equipment, File No. E132659
CSA 22.2 No. 274
CCC GB Standard
12350−2009
Chinese Compulsory Certificate
"Safety requirements of small−power motors"
Protection of persons and device protection
Enclosure EN 60529 IP55
IP54 for brake with manual
release
When ready for operation:
¯ Seal unused bore holes for cable glands by
means of blanking plugs!
¯ Seal unused connectors by means of protection
covers or blanking plugs!
¯ Close and bolt cover!
(Earth) leakage current EN 61800−5−1 > 3.5 mA AC, > 10 mA DC Observe regulations and safety instructions!
Total fault current In TN systems, the following earth−leakage circuit breakers may be used: 30 mA,
type B
Additional equipotential
bonding
M5−thread with terminal on terminal box for connection of a 6 mm
2
PE cable
Insulation of control circuits EN 61800−5−1
up to 2000 m amsl:
Safe mains isolation: Double/reinforced insulation for digital inputs and outputs
from 2000 m amsl:
If·an·overvoltage·protection·system·is·connected·upstream·to·the·device,·ad
ditional·external·measures·are·required·for·maintaining·the·safe·isolation.¶
Insulation resistance EN 61800−5−1
Site altitude
0 ... 2000 m Overvoltage category III
2000 ... 4000 m
from·2000
m·amsl:·external·measures·for·compliance·with·
the·overvoltage·category·II·are·required,·e.g.
¯ upstream·connection·of·transformer
¯ upstream·connection·of·overvoltage·protecti
on·system
Short−circuit strength EN 61800−5−1
Motor
To a limited extent, error acknowledgement
required
Motor holding brake
No
Brake resistor
No
Control terminals Yes
Earth fault resistance EN 61800−5−1
Connection:
Motor
To a limited extent, error acknowledgement
required
Brake resistor
No
Protective measures against ¯ Short circuit on the motor side during switch−on and during operation
¯ Motor stalling
¯ Motor overtemperature (I
2
xt monitoring)
Cyclic mains switching
¯ Switching
processes/minute
3
¯ Switching
processes/hour
Max. 20
¯ Pause Mains switching of three times per minute must be
followed by a pause of 9 min.