Testing
Leuze electronic MLC 510 40
9 Testing
NOTICE
Ä Safety sensors must be replaced at the end of their mission time (see chapter 14 "Technical
data").
Ä Always exchange entire safety sensors.
Ä Observe any nationally applicable regulations regarding the tests.
Ä Document all tests in a comprehensible manner and include the configuration of the safety
sensor along with the data for the safety- and minimum distances in the documentation.
9.1 Before commissioning and following modifications
WARNING
Unpredictable machine behavior during start-up may result in serious injury!
Ä Make certain that there are no people in the danger zone.
Ä Before they begin work, train the operators on their respective tasks. The training is the responsibility of
the operating company.
Ä Attach notes regarding daily testing in the respective national language of the operator on the machine
in a highly visible location, e.g. by printing out the corresponding chapter (see chapter 9.3 "Periodically
by the operator").
Ä Test the electrical function and installation according to this document.
Acc. to IEC62046 and national regulations (e.g. EU directive2009/104/EC), tests are to be performed by
competent persons (see chapter 2.2 "Necessary competencies") in the following situations:
Prior to commissioning
Following modifications to the machine
After longer machine downtime
Following retrofitting or new configuration of the machine
Ä As preparation, check the most important criteria for the safety sensor according to the following check-
list (see chapter 9.1.1 "Checklist for integrator – to be performed prior to commissioning and following
modifications"). Completing the checklist does not replace testing by competent persons (see chapter
2.2 "Necessary competencies")!
ð Not until proper function of the safety sensor is ascertained may it be integrated in the control circuit of
the system.
9.1.1
Checklist for integrator – to be performed prior to commissioning and following modifications
NOTICE
Completing the checklist does not replace testing by a qualified person (see chapter 2.2
"Necessary competencies")!
Ä If you answer one of the items on the following check list with no, the machine must no
longer be operated.
Ä IEC62046 contains additional recommendations on testing protective devices.
Tab.9.1: Checklist for integrator – to be performed prior to the initial start-up and following modifications
Check: Yes No not ap-
plicable
Is the safety sensor operated acc. to the specific environmental condi-
tions that are to be maintained (see chapter 14 "Technical data")?
Is the safety sensor correctly aligned and are all fastening screws and
connectors secure?

Table of Contents

Other manuals for Leuze electronic MLC 520 EX Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Leuze electronic MLC 520 EX Series and is the answer not in the manual?

Leuze electronic MLC 520 EX Series Specifications

General IconGeneral
BrandLeuze electronic
ModelMLC 520 EX Series
CategoryLighting Equipment
LanguageEnglish

Related product manuals