Function Code Ceiling height
Press button for 4 seconds
to enter the installer setting
mode until timer segment
display 01:01.
1
Repeat pressing button to select
Function code 05.
Ex) Setting Ceiling Height as 'Standard'.
2
Select ceiling height value by pressing
button.
(01:Low, 02:Standard, 03:High,
04:Super high)
3
Press button to save or release.
4
Press button to exit or
system will automatically exit
after 25 seconds without any
input.
5
16 Wide Wired Remote Controller
Installation instruction
Installer Setting -Ceiling Height Selection
This function is to adjust FAN Airflow rate according to ceilingheight (only cassette model)
Ceiling height setting is available only for some products.
Ceiling height of Super high function may not exist depending on the indoor unit.
Refer to the product manual for more details.
Ceiling Height Level Description
01 Low Decrease the indoor airflow rate 1 step from standard level
02 Standard Set the indoor airflow rate as standard level
03 High Increase indoor airflow rate 1 step from standard level
04 Super high Increase indoor airflow rate 2 steps from standard level