Chapter 7. SPECIAL MODULE COMMAND (BUFFER MEMORY READ/WRITE)
7 - 2
7.2 REMOTE COMMAND
Buffer Memory Write –RPUT
Sl
Upper(AB) : the code value of D/A conversion Module
G3F-DA3V:h42, G4F-DA3V:hC4, G4F-DA2V:hC3,
G6F-DA2V:h0A, G3F-DA3I:h41, G4F-DA3I:hC2,
G4F-DA2I:hC1, G6F-DA2I:h11
Lower(CD) : the slot number of communication
module of the master station(FUEA).
setting range: 0 to 7
Integer
St
Upper(EF): Slot number of D/A conversion module
of remote station.
setting range: 0 to 31
Lower(GH):Address number of communication module of
remote station(RBEA).
setting range :0 to 63
Integer
S Head address of special module which stores data to write. Integer
D Head address of device which stores data to write. M, P, K, L, T, C, D, #D
n Number of words of data to write. Integer, D
Ss Condition data display space of link M, P, K, L, T, C, D, #D
REMARK
To write on buffer memory data of D/A conversion modu
le with RPUT command, configure the program
so that execution condition of 0 will be changed into 1 on rising edge.
Otherwise buffer memory data of D/A conversion module won't be updated
[Buffer memory write]
1) Write data on D100 to D107(8words) of the CPU module device
2) onto buffer memory address 0 to 7 of D/A conversion module
3) and store the data of communication to D0.
[ RPUT SI St S D n SS]
RPUT command
execution condition
<Format>
PA2A
15AS
D22A
D22A
RY2A
RY2A
FUEA
PA2A
RBEA
D22A
DA3V
RPUT hC404 h010B D0100 00000 00007 D0000