Error Code Description Possible Cause
3 2 1
Master WSU inverter compressor discharge
temperature high
Compressor turned off due to Master WSU inverter compressor
discharge temperature too high
Master WSU ow rate insufcient or ow switch error
3 2 2
Slave 1 WSU inverter compressor discharge
temperature too high
Compressor turned off due to Slave 1 WSU inverter compressor
discharge temperature too high
Master WSU ow rate insufcient or ow switch error
3 2 3
Slave 2 WSU inverter compressor discharge
temperature too high
Compressor turned off due to Slave 2 WSU inverter compressor
discharge temperature too high
Slave 2 WSU ow rate insufcient or ow switch error
3 4 1 Master WSU high pressure too high
Compressor turned off due to Master WSU high pressure too high
Master WSU ow rate insufcient or ow switch error
3 4 2 Slave 1 WSU high pressure too high
Compressor turned off due to Slave 1 WSU high pressure too high
Slave 1 WSU ow rate insufcient or ow switch error
3 4 3 Slave 2 WSU high pressure too high
Compressor turned off due to Slave 2 WSU high pressure too high
Slave 2 WSU ow rate insufcient or ow switch error
3 5 1 Master WSU low pressure too low Compressor turned off due to Master WSU low pressure too low
3 5 2 Slave 1 WSU low pressure too low Compressor turned off due to Slave 1 WSU low pressure too low
3 5 3 Slave 2 WSU low pressure too low Compressor turned off due to Slave 2 WSU low pressure too low
3 6 1 Master WSU low pressure ratio Master WSU pressure ratio is under limit
3 6 2 Slave 1 WSU low pressure ratio Slave 1 WSU pressure ratio is under limit
3 6 3 Slave 2 WSU low pressure ratio Slave 2 WSU pressure ratio is under limit
4 0 1 Master WSU inverter compressor CT sensor error
Master WSU inverter compressor current detection (CT) sensor
disconnection or short circuit
4 0 2 Slave 1 WSU inverter compressor CT sensor error
Slave 1 WSU inverter compressor current detection (CT) sensor
disconnection or short circuit
4 0 3 Slave 2 WSU inverter compressor CT sensor error
Slave 2 WSU inverter compressor current detection (CT) sensor
disconnection or short circuit
4 1 1
Master WSU inverter compressor discharge
temperature sensor error
Master WSU inverter compressor discharge temperature sensor
disconnection or short circuit
4 1 2
Slave 1 WSU inverter compressor discharge
temperature sensor error
Slave 1 WSU inverter compressor discharge temperature sensor
disconnection or short circuit
4 1 3
Slave 2 WSU inverter compressor discharge
temperature sensor error
Slave 2 WSU inverter compressor discharge temperature sensor
disconnection or short circuit
4 2 1 Master WSU under-voltage sensor error Master WSU under-voltage sensor disconnection or short circuit
4 2 2 Slave 1 WSU under-voltage sensor error Slave 1 WSU under-voltage sensor disconnection or short circuit
4 2 3 Slave 2 WSU under-voltage sensor error Slave 2 WSU under-voltage sensor disconnection or short circuit
4 3 1 Master WSU over-voltage sensor error Master WSU over-voltage sensor disconnection or short circuit
4 3 2 Slave 1 WSU over-voltage sensor error Slave 1 WSU over-voltage sensor disconnection or short circuit