LG Multi V Water IV - Error Code Tables: Water Source Unit Errors (Part 3); Water Source Unit Error Codes (Section 3)

LG Multi V Water IV
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
119
Error Codes
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Error Code Description Possible Cause
4 3 3 Slave 2 WSU over-voltage sensor error Slave 2 WSU over-voltage sensor disconnection or short circuit
4 4 1 Master WSU air temperature sensor error Master WSU air temperature sensor disconnection or short circuit
4 4 2 Slave 1 WSU air temperature sensor error Slave 1 WSU air temperature sensor disconnection or short circuit
4 4 3 Slave 2 WSU air temperature sensor error Slave 2 WSU air temperature sensor disconnection or short circuit
4 5 1
Master WSU heat exchanger temperature
sensor (A) fault
Master WSU heat exchanger temperature sensor (A) open or short
4 5 2
Slave 1 WSU heat exchanger temperature
sensor (A) fault
Slave 1 WSU heat exchanger temperature sensor (A) open or short
4 5 3
Slave 2 WSU heat exchanger temperature
sensor (A) fault
Slave 2 WSU heat exchanger temperature sensor (A) open or short
4 6 1 Master WSU suction temperature sensor error Master WSU suction temperature sensor disconnection or short circuit
4 6 2 Slave 1 WSU suction temperature sensor error Slave 1 WSU suction temperature sensor disconnection or short circuit
4 6 3 Slave 2 WSU suction temperature sensor error Slave 2 WSU suction temperature sensor disconnection or short circuit
4 9 1 Master WSU IPM temperature sensor error Master WSU IPM temperature sensor disconnection or short circuit
4 9 2 Slave 1 WSU IPM temperature sensor error Slave 1 WSU IPM temperature sensor disconnection or short circuit
4 9 3 Slave 2 WSU IPM temperature sensor error Slave 2 WSU IPM temperature sensor disconnection or short circuit
5 0 1 Master WSU input power phase loss Master WSU has lost one of the phases of the three-phase power input
5 0 2 Slave 1 WSU input power phase loss Slave 1 WSU has lost one of the phases of the three-phase power input
5 0 3 Slave 2 WSU input power phase loss Slave 2 WSU has lost one of the phases of the three-phase power input
5 1 1
Over-capacity (Indoor unit capacity sum is
excessive) connection
Excessive connection of indoor unit connection (combination ratio is
exceeded)
5 2 1 Master WSU inverter controller communication error
Inverter controller signal is not received from the Master WSU inverter
controller
5 2 2
Slave 1 WSU inverter controller communication
error
Inverter controller signal is not received from the Slave 1 WSU inverter
controller
5 2 3
Slave 2 WSU inverter controller communication
error
Inverter controller signal is not received from the Slave 2 WSU inverter
controller
5 3 1
Communication error between WSU controller and
indoor unit
Indoor unit control signal is not received from the WSU inverter controller
5 7 1 Master WSU inverter controller communication error Inverter controller signal not received by Master WSU controller
5 7 2
Slave 1 WSU inverter controller communication
error
Inverter controller signal not received by Slave 1 WSU controller
5 7 3
Slave 2 WSU inverter controller communication
error
Inverter controller signal not received by Slave 2 WSU controller
5 9 1 Series connection error Connection error between WSUs
6 0 1 Master WSU inverter PCB EEPROM error Master WSU inverter PCB EEPROM ACCESS error
6 0 2 Slave 1 WSU inverter PCB EEPROM error Slave 1 WSU inverter PCB EEPROM ACCESS error
6 0 3 Slave 2 WSU inverter PCB EEPROM error Slave 2 WSU inverter PCB EEPROM ACCESS error
Table 76: Water Source Unirt Error Codes - continued
ERROR CODE TABLES