125
INSTALLER SETTING
ENGLISH
Water Flow Control
This function controls the water flow by controlling the water pump. Select the way to control
the water pump and set the target value
• In the installer setting list, select Configuration category, and press [OK] button to move to the
detail screen.
• Optimal Flow Rate
The water pump is automatically controlled at the optimum flow rate required according to the
desired temperature of the Main screen.
• Pump Capacity
It operates with the capacity set for the water pump.
• Fixed Flow Rate
The water pump is automatically controlled to maintain the set flow rate.
• Fixed ΔT
Set the target ΔT (*ΔT = temperature difference between inlet and outlet water temperature)
The water pump is automatically controlled to maintain the set ΔT.
OK
Flow Control Method
Optimal Flow Rate
(Default)
Pump Capacity Fixed Flow Rate
Fixed ΔT