EasyManuals Logo

LG THERMA V HN0913T User Manual

LG THERMA V HN0913T
189 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #127 background imageLoading...
Page #127 background image
127
INSTALLER SETTING
ENGLISH
Anti-Freezing Option 1
This function is to select whether to use Type1 or Type2 to prevent freezing when the remote
control is turned off.
• Change setting values using [<,>(left/right)] button.
Value
Type1(Default) Type2
CAUTION
If the function is set to Type 2, there is a risk of freezing.
!
Function Detection Case Operation
Type 1
Type 2 + Inlet
Temp.
Air Temp. < Certain Level
Inlet Temp. < Certain Level
Pump always ON
Air Temp. < Certain Level
Inlet Temp. > Certain Level
Pump intermittently On
Air Temp. > Certain Level
Inlet Temp. > Certain Level
Pump always OFF
Type 2 Air Temp.
Air Temp. < Certain Level Pump intermittently On
Air Temp. > Certain Level Pump always OFF

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG THERMA V HN0913T and is the answer not in the manual?

LG THERMA V HN0913T Specifications

General IconGeneral
BrandLG
ModelTHERMA V HN0913T
CategoryHeat Pump
LanguageEnglish

Related product manuals