Liebert Hinet 20kVA - Clearances; Raised Floor Installation; Cable Entry; UPS Mechanical Characteristics

Liebert Hinet 20kVA
43 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Hinet UPS User Manual
Page 6 (12/01)
- enough space to easily work on UPS;
- exchange of air sufficient enough to dispel heat produced by UPS;
- protection against atmospheric agents;
- protection against excessive humidity and very high heat sources;
- protection against dust;
- compliance with the current fire prevention norms.
- operative environment temperature within +20° C and +25° C. The batteries are at maximum efficiency in this
temperature range.
2.1.6 Clearances
Cooling air enters the module through ventilation grills located at the bottom of the cabinet and is exhausted through the
fan grills located on the front panel; you must therefore allow for a minimum gap of 170 mm behind the unit to allow
adequate air flow. Clearance around the front of the equipment should be sufficient to enable free passage of personnel
with the door fully opened.
2.1.7 Raised floor installation
If the equipment is to be located on a raised floor it must be mounted on a pedestal suitably designed to accept the
equipment point loading. Refer to the base view to design this pedestal.
2.1.8 Cable entry
Cables can enter for 'Hinet' UPS cabinet from rear side.
2.1.9 UPS Mechanical Characteristics
MECHANICAL
CHARACTERISTICS
UNITS
Rated power kVA 10 15 20 30
Height
mm 1220
Width
mm 530
Depth
mm 950
Weight:
Hinet cabinet
185
with 1 battery strings
275
with 2 battery strings
365
with 3 battery strings
Kg
455
with 4 battery strings
545
Unit Shipping Weight
With Standard Battery
320 410 410 500
Colour
RAL 7035 Metal Covers
RAL 7042 Plastic Door
Ventilation
- forced
Air flow full speed
Air flow half speed
m
3
/h
600
300
Protection grade
- IP 20
Cable entry
- Bottom