pag. 12
Tab. 4 -- 50 Hz Technical da ta f or ”COOLING ONLY” and “COOLING + HEATING” unit versions
(F and F+C) coupled with “HPSCxxA/L”
Model HPS 06 HPS 08 HPS 10 HPS 12 HPS 14
Operating limits
Main power supply voltage
230V ±10%
/1Ph/50Hz
400V ±10% / 3Ph+N+PE / 50Hz
*
from : --- 3 0 °C
Outdoor conditions
to: 51°C 50°C
from : 24°C, 30% R.H / 80% R.H.
(**)
Indoor conditions with compressor running
to:
34°C,
40% R.H.
30°C, 40% R.H.
from : --- 4 0 °C, 5% R.H.
Storage conditions
to: 55°C, 90% R.H.
Sound pressure level
Outdoor sound pressure level
(1)
dB(A) 48.5 48.5 52.5 53.5 55.0
Indoor sound pressure level dB(A) 58.0 62.5 62.5 64.0 64.0
Standard electrical features
Compressor --- AC power input
(2)
kW 1.73 2.23 3.06 3.75 4.68
Compressor --- AC operative current (OA)
(2)
A 8.0 4.0 5.5 6.6 8.6
Compressor --- AC max. current (FLA) A 11.4 5.1 7.0 10.0 10.2
Compressor --- AC starting current (LRA) A 47.0 32.0 46.0 50.0 63.0
Condenser fan --- AC power input
(2)
kW 0.07 0.10 0.22 0.22 0.28
Condenser fan --- AC max. power input kW 0.24 0.24 0.48 0.48 0.48
Condenser fan --- AC operative current (OA)
(2)
A 0.6 0.7 1.5 1.5 1.7
Condenser fan --- AC max. current (FLA) A 1.4 1.4 2.8 2.8 2.8
Condenser fan --- AC max. current (FLA) A 1.6 1.6 3.3 3.3 3.3
Evaporator f an --- AC power input
(2)
kW 0.18 0.35 0.35 0.34 0.34
Evaporator fan --- AC operative current (OA)
(2)
A 0.8 1.5 1.5 2.0 2.0
Evaporator fan --- AC max. current (FLA)
(3)
A 1.0 2.0 2.0 2.0 2.0
Evaporator fan --- AC starting current A 1.3 2.7 2.7 2.7 2.7
Electric heating (optional)
Heating capacity kW 1.5 3.0 3.0 4.5 6.0
H e a t i n g --- m a x . c u r r e n t A 6.5 13.0
OA: Standard Operating Ampère
FLA: Full Load Ampère
LRA: Locked Rotor Ampère
Notes:
(*)
Maximum outdoor temperature referred to 30ûC / 35% R.H. indoor unit air suction (HPSE).
(**)
Conditions referred to the suction sections of the inner unit (HPSE); the min. indoor temperature is referred to 30% of indoor relative humidity and to the min.
outdoor temperature; for higher relative humidity and/or outdoor temperatures, the min. indoor temperature is higher than the table data.
(1)
Measured with 35ûC o utdoor temperature at 2m far from the unit; free field conditions.
(2)
Indoor reference conditions: 30ûC / 35% R.H. at the HPSE indoor unit air suction sides; 35ûC outdoor. Nominal power supply.
(3)
It refers to nominal speed (Factory setting).