FlexPower DC Power System Installation Manual
10 11
Specifications
Section 3 – Specifications
3.1 Electrical Specifications
FPO Power Supplies
Specifications FPO75 FPO150 FPO250
AC Input Voltage 120VAC or 230VAC
±15% at 50-60Hz
120VAC or 230VAC
±15% at 50-60Hz
120VAC or 230VAC
±15% at 50-60Hz
Current 1.6A 2.5A 3.2A
Standby Current 100mA 100mA 100mA
Rated Current for UL603 Proprietary
Alarm Installations
Current 1.25A maximum from
all circuits in system
2.5A maximum from
all circuits in system
2.5A maximum from
all circuits in system
DC Output at 12V Setting Voltage 11.3 -12.0V 11.3 -12.0V 11.3 -12.0V
Max Current 6A Alarm 4.5A
Nominal Supervisory
12A Alarm
Nominal Supervisory
12A Nominal Super-
visory
Ripple 120mV 120mV 120mV
Regulation ±2% ±2% ±2%
Efficiency 85% (120VAC
60Hz In, Full Load,
No Batt)
88% (120VAC
60Hz In, Full Load,
No Batt)
89% (120VAC
60Hz In, Full Load,
No Batt)
DC Output at 24V Setting Voltage 23.5-24.0 23.5-24.0 23.5-24.0
Max Current 3A 6A 10A
Ripple 120mV 120mV 120mV
Regulation ±2% ±2% ±2%
Efficiency 85% (120VAC
60Hz In, Full Load,
No Batt)
88% (120VAC
60Hz In, Full Load,
No Batt)
89% (120VAC
60Hz In, Full Load,
No Batt)
Battery Size & Type 4-40AH Lead Acid
or Gel Cell
4-80AH Lead Acid
or Gel Cell
4-80AH Lead Acid
or Gel Cell
Charge
Current
1A (±10%) Maximum
(Adjustable via
PowerCom Software)
2A (±10%) Maximum
(Adjustable via
PowerCom Software)
2A (±10%) Maximum
(Adjustable via
PowerCom Software)
Fuse Ratings DC1 ATM 7.5A ATM 15A ATM 30A
DC2 ATM 7.5A ATM 15A ATM 30A
Battery ATM 7.5A ATM 15A ATM 30A
BTU Output BTU 33 66 109
Fault Setpoints Low AC 95V (±6%) 95V (±6%) 95V (±6%)
Earth GND 2000 Ohms 2000 Ohms 2000 Ohms
Output Voltage ±10% of nominal ±10% of Nominal ±10% of Nominal
Batt Voltage ±10% of nominal ±10% of Nominal ±10% of Nominal
Batt Presence 6–15V (12V Setting),
11–29V (24V Setting)
6–15V (12V Setting),
11–29V (24V Setting)
6–15V (12V Setting),
11–29V (24V Setting)
Fault Relay Contacts AC FLT 1A at 24VDC 1A at 24VDC 1A at 24VDC
SYS FLT 1A at 24VDC 1A at 24VDC 1A at 24VDC