REMOTE DEVICE WIRING REQUIREMENTS
Cable Type
Each remote device requires a 6-wire connection to the AM/II.
Depending on the distance of the cable run, two different types
of cable are recommended.
For cable distance up to 300 feet, use BELDEN 9931
(24 AWG).
For cable distance up to 500 feet, use WEICO 9405
(20 AWG).
Load Number
Each hardwired remote accessory device has been assigned
a “load number”. Homerun wiring is recommended for
accessories, although multiple accessories can be wired on the
same cable run if the following formulas are used.
For cable distance up to 300 feet:
CABLE RUN IN FEET x LOAD UNITS = 3,000 OR LESS
For cable distance up to 500 feet:
CABLE RUN IN FEET x LOAD UNITS = 10,000 OR LESS
REMOTE DEVICE LOAD NUMBER
AM-KP 9
AM-RRR 4
AM-CRI 25
AM-RPR 4