EasyManua.ls Logo

Liquid Controls LectroCount3

Default Icon
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36
If the above voltages are correct:
This may indicate a mechanical problem with the valve or its associated components. Refer the
problem to a qualified Liquid Controls Service Center.
If the above voltages are NOT correct:
Replace the following components with known-working units until the problem is resolved:
CPU Board* (part # 81204)
Signal Harness (part # 81340)
*Contact your local Liquid Controls Service Center or contact the Liquid Controls Customer Service
Department for assistance.
PROBLEM: Valve will not open (Dual Stage).
PROBABLE CAUSE: Solenoids Inactive / Inoperative.
SOLUTION:
1) Remove the (12) 7/16” bolts securing the REC cover. Lift the cover and remove the coiled
phone cable. Set the cover to the side, taking care not to damage the phone-type cable
connector.
2) Using a reliable voltmeter, measure the following DC voltages on the REC board ( part #
81268)
Terminal # Voltage
J4 # 20 1.0VDC ± .5VDC
J4 # 21 12.0VDC ± 1.5VDC
J4 # 22 1.0VDC ± .5VDC
J4 # 23 12.0VDC ± 1.5VDC
If the above voltages are correct:
This may indicate a mechanical problem with the valve or its associated components. Refer the
problem to a qualified Liquid Controls Service Center.
If the above voltages are not correct:
Replace the following components with known-working units until the problem is resolved:
CPU Board* (part # 81204)
Signal Harness (part # 81340)
*Contact your local Liquid Controls Service Center or contact the Liquid Controls Service center for
assistance.
TROUBLESHOOTING

Table of Contents

Related product manuals