99
Frequency
Detection Level
Sets the detection level and width for the
multi-function output terminal.
Default: 30.0 Hz
Min.: 0.0 Hz
Max.: 2000 hz
Frequency
Detection Width
Default: 2.0 Hz
Min.: 0.1 Hz
Max.: 25.5 Hz
Frequency
Command Loss
Detection Selection
Sets the drive operation when a frequency
command loss is detected.
0: Drive Stop
1: Continue operation according to the setting in
P4-03.
Frequency
Command at
Frequency
Command Loss
Sets the frequency command level at which the
drive runs when detecting a frequency command
loss and when L4-02 is set to 1. Sets the value as a
percentage of the maximum output frequency set
in d1-02. (Sets the value as a percentage of the
motor 2 maximum output frequency set in d1-13.)
Default: 80%
Min.: 0.0 %
Max.: 100.0 %
Frequency Command
Loss Detection Time
When the frequency command falls below 90% of
the command within this detection time, the
frequency command loss will be detected.
Default: 20ms
Min.: 20 ms
Max.: 400 ms
Mechanical brake
release frequency
Sets the mechanical brake release frequency
Default: 0.00 HZ
Min.: 0.00
Max.: 20.00
Mechanical braking
frequency
Sets the mechanical braking frequency
Default: 0.00 HZ
Min.: 0.00
Max.: 20.00
Number of Auto
Restart Attempts
Sets the number of times to automatically
attempt to restart the drive when detecting GF,
OVA, OVD, OVC, OCA, OCD, OCC, OH, OL1, OL2,
OT1, OT2, PF and LF1.
Default: 0
Min.: 0
Max.: 10
Auto Restart Fault
Output Operation
0 : Fault Output Disabled
1 : Fault Output Enabled
Sets the amount of time between restart