102
1 : Enabled when One Phase is Lost
2 : Enabled when Two Phases are Lost
Output Ground
Fault Detection
Enables or disables the output ground fault
detection.
0 ∶ Disabled
1 ∶ Enabled
Heatsink Cooling
Fan Operation <6>
Sets the heatsink cooling fan operation.
0 : Enabled when drive is running
1 : Enabled when power supply is On
2 : Enabled when the heatsink temperature
reaches the limit.
Heatsink Cooling
Fan Off-Delay Time
When P7-04=0, sets the cooling fan off-delay time
that the drive waits to disabled the cooling fan
after run command is released.
Default: 60 s
Min.: 0 s
Max.: 300 s
OL2 decreasing
curve selection
0: Same as before V1.10, it takes 4 minutes for
OL2 to decrease from 100% to 0%.
1: HD mode, 100% load, OL2 from 100% to 0%
takes 4 minutes, load 40%, OL2 from 100% to 0%
takes 1 minute; ND2, OL2 drops from 100% to 0 %
takes 4 minutes
High Current Alarm
Setting
Sets the High Current Alarm (HCA) when the
output current is too high
0 : Disabled (No Alarm)
1 : Enabled (Alarm)
Installation Method
Selection
Selects the installation type. The drive overload
detection limit will be changed according to the
selection.
0 : IP20 Enclosure in a Cabinet
1 : Side-by-Side Mounting
2 : NEMA 1 Enclosure
Sets the DC braking transistor level.
Default: Determined by
d1-00 <3><8>
Range: 330~400 V ,3>
Turn on/off standby precharge
0 : Close
1 : Open
Group n, Special Adjustments