101
Parameter
Name
Description
Setting Range
above P6-07
3 : Stop Operation if the Speed (Signed) is above
P6-07
4 : Stop Operation if the Speed (Unsigned) is
above P6-07
5 : Continue Operation if the Speed (Signed) is
below P6-07
6 : Continue Operation if the Speed (Unsigned) is
below P6-07
7 : Stop Operation if the Speed (Signed) is below
P6-07
8 : Stop Operation if the Speed (Unsigned) is
below P6-07
P6-07
Mechanical
Weakening
Detection Speed
Level
Sets the speed level for Mechanical Weakening
Detection as a percentage of the maximum output
frequency.
Default: 110.0%
Min.: -110.0%
Max.: 110.0%
P6-08
Mechanical
Weakening
Detection Time
If the condition set in P6-06 lasts the time set in
this parameter, Mechanical Weakening is
detected.
Default: 0.1 s
Min.: 0.0 s
Max.: 10.0 s
P6-09
Mechanical
Weakening
Detection Start
Time
Sets the cumulative drive operation time to
activate Mechanical Weakening Detection. If
U3-00 reaches the value set in this parameter,
Mechanical Weakening is detected.
Default: 0
Min.: 0
Max.: 65535
P6-10
Forward Torque
Limit
Sets the torque limits as a percentage of the
motor rated torque.
Default: 200%
Min.: 0%
Max.: 300%
P6-11
Reverse Torque
Limit
Default: 200%
Min.: 0%
Max.: 300%
P6-12
Forward
Regenerative
Torque Limit
Default: 200%
Min.: 0%
Max.: 300%
P6-13
Reverse
Regenerative
Torque Limit
Default: 200%
Min.: 0%
Max.: 300%
P7: Drive Protection
P7-00
Input Phase Loss
Protection
Enables or disables the input phase loss detection.
0 Disabled
1 Enabled
Default: 15 V <3>
Min.: 0 V
Max.: 30 V <3>
P7-01
Output Phase Loss
Protection
Sets the output phase loss detection.
0 : Disabled
Default: 0
Range: 0, 1