110
Parameter
Name
Description
Setting Range
When 0 is set to either F1-14 or F1-15, the ratio
will be 1.
F1-15
PG Number of Gear
Teeth 2
Sets the number of the gear teeth (ratio) on the
machinery side between the motor shaft and PG
encoder.
When 0 is set to either F1-14 or F1-15, the ratio
will be 1.
Default: 1
Min.: 1
Max.: 6000
F1-16
PG dv3 (Inversion
Detection)
Detection Setting
0 Disabled
n Sets the number of detection times to trigger
dv3.
Default: 10 times
Min.: 0 times
Max.: 10 times
F1-17
PG dv4 (Inversion
Prevention
Detection)
Detection Setting
0 Disabled
n Sets the number of pulses to trigger dv4
Default: 128
Min.: 0
Max.: 5000
F1-18
Resolver offset
angle
Angle deviation between the angle of the angler
and the actual shaft
183 scale corresponds to a mechanical angle of 1
degree
Default: 0
Min.: 0
Max.: 22000
F1-19
Pulse input method
Upper control pulse input detection method
0: A/B phase checkout
1: Phase A speed detection, phase B direction
detection
Default: 0
Range: 0 to 1
F1-20
PG error handling
How PG or Resolver handles errors when
returning:
0: no action
1: Warning
2: Protection output (Fault)
Default: 1
Min.: 0
Max.: 2
F1-21
PG zero speed
return time
The zero speed judgment detects the number of
seconds. If there is no signal input within the set
time, it is determined to be zero speed. If set to 0,
it is automatically recognized.
Default: 0
Min.: 0
Max.: 100
F1-22
Dv4 error detection
delay time
Default: 0.1 s
Min.: 0.1 s
Max.: 2.0 s
F1-23
Speed feedback
moving average
filter value
Default: 0
Min.: 0
Max.: 100
F2: Sets for Communication Purchase
F2-00
Retain
F2-01
<9>
CANopen
communication
Sets the slave station of the CANopen
communication of the inverter
Default: 1
Min.: 1