109
Sets the division ratio of pulse output for a PG
card. Set X for a ratio of 1/X.
When only A pulse is set, monitor pulse output
will be 1:1 regardless of the setting in F1-02.
Default: 1
Min.: 1
Max.: 255
0 ∶ Channel A Only
1 ∶ Channels A and B
PG Disconnection
Detection
0 ∶ PG or No option card
1 ∶ Resolver card
PG Open (PGo)
Operation Setting
Sets the operation for a PGo fault.
0: Ramp to Stop (Active Deceleration ))
1: Coast to Stop
2: Alarm Only
Default: 1
Range: 0, 1, 2
PG Open (PGo)
Detection Time
Sets the time to detect the signal before triggering
PGo fault.
Default: 2.0 sec
Min.: 0.0 s
Max.: 10.0 s
Overspeed (oS)
Operation Setting
Sets the operation for an oS fault.
0: Ramp to Stop (Active Deceleration )
1: Coast to Stop
2: Alarm Only
Default: 1
Range: 0, 1, 2
Overspeed (oS)
Detection Level
Sets the Overspeed (oS) detection level as a
percentage of the maximum output frequency
(d1-02). An oS fault will be triggered if the motor
speed feedback is greater than the level set in
F1-09 for longer than the delay time set in F1-10.
Motor speed feedback = F1-09 *d1-02.
Default: 115%
Min.: 0 %
Max.: 120 %
Overspeed (oS)
Detection Delay
Time
Default: 0.5 sec
Min.: 0.0 sec
Max.: 2.0 sec
Speed Deviation
(dEv) Operation
Setting
Sets the operation for a dEv fault.
0: Ramp to Stop (Active Deceleration )
1: Coast to Stop
2: Alarm Only
Default: 2
Range: 0, 1, 2
Speed Deviation
(dEv) Detection
Level
Sets the speed deviation (dEv) detection level as a
percentage of the maximum output frequency
(d1-02). A dEv fault will be triggered if the
difference between the motor speed feedback
and frequency command is greater than the level
set in F1-12 for longer than the delay time set in
F1-13.
Default: 10%
Min.: 0 %
Max.: 50 %
Speed Deviation
(dEv) Detection
Delay Time
Default: 0.5 sec
Min.: 0.0 sec
Max.: 10.0 sec
PG Number of Gear
Teeth 1
Sets the number of the gear teeth (ratio) on the
motor side between the motor shaft and PG
encoder.
Default: 1
Min.: 1
Max.: 60000