108
Sets the PM motor base speed according to the
motor nameplate.
Default∶
1750 rpm
Min.: 0 rpm
Max.: 24000 rpm
PM Motor Rotor
Resistance
Sets the PM motor rotor resistance per phase
according to the motor nameplate.
Default: 0.000Ω
Min.: 0.000 Ω
Max.: 65.000 Ω
PM Motor d-Axis
Inductance
Sets the PM motor d-axis inductance according to
the motor nameplate.
Default: 0.00 mH
Min.: 0.00 mH
Max.: 600.00 mH
PM Motor q-Axis
Inductance
Sets the PM motor d-axis inductance according to
the motor nameplate.
Default: 0.00 mH
Min.: 0.00 mH
Max.: 600.00 mH
PM Motor Induced
Voltage Constant
(Ke)
Sets the PM motor induced voltage constant
according to the motor nameplate.
Default: 0.1
Min.: 0.1
Max.: 2000.0
PM Motor
Auto-Tuning Current
Sets the amount of current for Auto-Tuning as a
percentage of the motor rated current. Increase
this value when inertia is high.
Default: 30%
Min.: 0%
Max.: 120%
PG pulse number
when PM motor is
automatically
commissioned
Set the number of pulses per revolution of the PM
motor using PG (pulse generator, encoder).
Default: 2500 ppr
Min.: 1 ppr
Max.: 15000 ppr
PM Motor
Auto-Tuning Setting
Default∶ 0
Min.: 0
Max.: 1
Sets the number of pulses (pulse generator and
encoder) per resolution for PG.
Default: 1024 ppr
Min.: 1 ppr
Max.: 15000 ppr
Selects the direction indicated by the PG pulses.
0 ∶ A pulse leads with Forward fun command.
1 ∶ B pulse leads with Forward fun command.
Default: Determined by
A1-02
Range: 0, 1