66
Parameter
Name
Description
Setting Range
power up
1
Accept
Drive accepts an active run command at power
up and runs the motor immediately.
b1-11
Retain
b1-12
<7>
Allow LO/RE switching
selection during
operation
0: Invalid
1: Valid
Default
0
Min.: 0
Max.: 1
b2: DC Braking
b2-00
Zero Speed Holding
(DC Braking) Start
Level
Sets the start frequency for Zero Speed Holding
(DC braking). Enabled when b1-02 (Stopping
Method Selection) is set to 0 (Ramp to Stop)
Default
0.5Hz
Min.: 0.0 Hz
Max.:
d1-02
b2-01
DC Braking Current
Sets the DC braking current as a percentage of the
drive rated current
Default
0%
Min.: 0%
Max.: 100%
b2-02
DC Braking Time at
Start
Sets the DC braking time at start to stop a
coasting motor before restarting it or to apply
braking torque at start when high starting torque
is needed.
Disabled when set to 0.00.
Default
0.00 s
Min.: 0.00 s
Max.: 99.99 s
b2-03
DC Braking Time at
Stop
Sets the DC braking time at stop to stop a motor
rotating with high inertia.
Disabled when set to 0.00.
Default
0.00 s
Min.: 0.00s
Max.: 99.99s
b2-04
Reserved
b2-05
DC braking decay
time
Default
0.1 s
Min.: 0 s
Max.: 5.00s
b3: Speed Search
b3-00
Speed Search
Setting
0
Disabled
1
Enabled and searched from the highest
frequency
2
Enabled and searched from the frequency
command
3
Retain
4
Retain
Default: 0
Min.: 0
Max.: 2
b3-01
Speed Search
Operating Current
Sets the current level as a percentage of the drive
rated current below which Speed Search is
deactivated.
Default: 120%
Min.: 30 %
Max.: 140%
b3-02
Voltage recovery
Set the time required to restore the output
Default: 0.6 s