66
power up
1
∶
Accept
Drive accepts an active run command at power
up and runs the motor immediately.
Allow LO/RE switching
selection during
operation
Default
∶
0
Min.: 0
Max.: 1
Zero Speed Holding
(DC Braking) Start
Level
Sets the start frequency for Zero Speed Holding
(DC braking). Enabled when b1-02 (Stopping
Method Selection) is set to 0 (Ramp to Stop)
Default
∶
0.5Hz
Min.: 0.0 Hz
Max.:
d1-02
Sets the DC braking current as a percentage of the
drive rated current
Default
∶
0%
Min.: 0%
Max.: 100%
Sets the DC braking time at start to stop a
coasting motor before restarting it or to apply
braking torque at start when high starting torque
is needed.
Disabled when set to 0.00.
Default
∶
0.00 s
Min.: 0.00 s
Max.: 99.99 s
Sets the DC braking time at stop to stop a motor
rotating with high inertia.
Disabled when set to 0.00.
Default
∶
0.00 s
Min.: 0.00s
Max.: 99.99s
Default
∶
0.1 s
Min.: 0 s
Max.: 5.00s
0
∶
Disabled
1
∶
Enabled and searched from the highest
frequency
2
∶
Enabled and searched from the frequency
command
3
∶
Retain
4
∶
Retain
Default: 0
Min.: 0
Max.: 2
Speed Search
Operating Current
Sets the current level as a percentage of the drive
rated current below which Speed Search is
deactivated.
Default: 120%
Min.: 30 %
Max.: 140%
Set the time required to restore the output