67
voltage to the set V/F curve voltage during speed
search
Speed search
deceleration time
Set the deceleration time in the speed finding
action (the time until the highest output
frequency decelerates to the lowest output
frequency.
Default
∶
2.0 s
Min.: 0.1 s
Max.: 10.0 s
In order to reduce the output current in the speed
search, the voltage calculated by the V/F curve is
multiplied by the set value of b3-05. By adjusting
this setting, the output current in the speed
search can be suppressed.
Default
∶
100%
Min.: 10%
Max.: 100%
ASR proportional (P)
gain during speed
search
Default
∶
0.6
Min.: 0.01
Max.: 30.00
ASR integral (I) gain
during speed search
Default
∶
2.80
Min.: 0.01
Max.: 30.00
Speed search
feedback filter
Set the speed of the motor to feedback the
low-pass filter time during speed search
Default
∶
0.1 s
Min.: 0 s
Max.: 1.000 s
Timer Function
On-Delay Time
Sets the on-delay and off-delay time to switch
on/off the timer output.
Default
∶
0.1 s
Min.: 0.1 s
Max.: 3000.0 s
Timer Function
Off-Delay Time
Default
∶
0.1 s
Min.: 0.0 s
Max.: 3000.0 s
0
∶
PID Control Disabled
1
∶
PID Control Enabled (D Control for Deviation
Signal U4-01)
2
∶
PID Control Enabled (D Control for Feedback
Signal U4-05)
3
∶
PID Control Enabled (Frequency Command
+
PID Output from D Controlled Deviation)
4
∶
PID Control Enabled (Frequency Command
+
PID Output from D Controlled Feedback)
5: PID control is invalid, but b5-14/b5-15 (PID
Default
∶
0
Min.: 0
Max.: 6