69
Parameter
Name
Description
Setting Range
2
Feedback Low /High Fault
A fault will cause the drive to stop the motor.
3
Multi-Function Output only when PID is
Disabled
Same action as b5-11=0.
4
Feedback Low /High Alarm (detection disabled
when PID is disabled)
5
Feedback Low /High Fault (detection disabled
when PID is disabled)
6 : Multi-function output, no light faults continue
to operate
7 : Multi-function contacts only (non-operational
detection is still valid)
b5-12
PID Feedback Low
Detection Level
Sets the PID feedback level used for detection.
When the PID feedback falls below this level for
longer than the time set to b5-13, PID feedback
loss will be detected.
Default
0%
Min.: 0%
Max.: 100%
b5-13
PID Feedback Low
Detection Time
Sets the PID feedback time used for detection.
When the PID feedback falls below the level set to
b5-12 for longer than this time, PID feedback loss
will be detected.
Default
1.0 s
Min.: 0.0 s
Max.: 25.5 s
b5-14
PID Sleep Start
Level
Sets the PID level to trigger the drive to sleep.
Default
0.0Hz
Min.: 0.0 Hz
Max.: <5>
b5-15
PID Sleep Delay
Time
Sets the delay time used to activate/deactivate
the PID Sleep function.
Default
0.0 s
Min.: 0.0 s
Max.: 25.5 s
b5-16
PID Command
Acc./Dec. Time
Sets the PID command acceleration /deceleration
time used for PID target.
Default
0.0 s
Min.: 0.0 s
Max.: 20.0 s
b5-17
PID Target Selection
0
PID Target Disabled
1
PID Target Enabled
Default
0
Min.: 0
Max.: 1
b5-18
PID Target Value
Sets the PID target value as a percentage of the
maximum output frequency when b5-17 is set to
1. Disabled when b5-17=0
Default
0.00%
Min.: 0.00%
Max.: 100.00%
b5-19
PID Target Value
Units
0
0.01Hz
1
0.01% (Maximum Frequency is 100%)
2
r/min. (Number of Motor Poles must be set)
3
User Defined (Defined by b5-24 and b5-25)
Default
1
Min.: 0
Max.: 3
b5-20
PID output lower
The lower limit value can be set to avoid the
Default
0.0%