69
2
∶
Feedback Low /High Fault
A fault will cause the drive to stop the motor.
3
∶
Multi-Function Output only when PID is
Disabled
Same action as b5-11=0.
4
∶
Feedback Low /High Alarm (detection disabled
when PID is disabled)
5
∶
Feedback Low /High Fault (detection disabled
when PID is disabled)
6 : Multi-function output, no light faults continue
to operate
7 : Multi-function contacts only (non-operational
detection is still valid)
PID Feedback Low
Detection Level
Sets the PID feedback level used for detection.
When the PID feedback falls below this level for
longer than the time set to b5-13, PID feedback
loss will be detected.
Default
∶
0%
Min.: 0%
Max.: 100%
PID Feedback Low
Detection Time
Sets the PID feedback time used for detection.
When the PID feedback falls below the level set to
b5-12 for longer than this time, PID feedback loss
will be detected.
Default
∶
1.0 s
Min.: 0.0 s
Max.: 25.5 s
Sets the PID level to trigger the drive to sleep.
Default
∶
0.0Hz
Min.: 0.0 Hz
Max.: <5>
Sets the delay time used to activate/deactivate
the PID Sleep function.
Default
∶
0.0 s
Min.: 0.0 s
Max.: 25.5 s
PID Command
Acc./Dec. Time
Sets the PID command acceleration /deceleration
time used for PID target.
Default
∶
0.0 s
Min.: 0.0 s
Max.: 20.0 s
0
∶
PID Target Disabled
1
∶
PID Target Enabled
Default
∶
0
Min.: 0
Max.: 1
Sets the PID target value as a percentage of the
maximum output frequency when b5-17 is set to
1. Disabled when b5-17=0
Default
∶
0.00%
Min.: 0.00%
Max.: 100.00%
0
∶
0.01Hz
1
∶
0.01% (Maximum Frequency is 100%)
2
∶
r/min. (Number of Motor Poles must be set)
3
∶
User Defined (Defined by b5-24 and b5-25)
Default
∶
1
Min.: 0
Max.: 3
The lower limit value can be set to avoid the