79
Default: 50.00Hz
Min.: 0.00Hz
Max.: <5>
Default: 50.00Hz
Min.: 0.00Hz
Max.: <5>
Sets the Jog frequency command.
Default: 6.00 Hz
Min.: 0.00Hz
Max.: <5>
L2: Frequency Upper/ Lower Limit
Frequency
Command Upper
Limit
Sets the upper limit as a percentage of the
maximum output frequency
Default: Determined by
d1-02
Min.: 0.0 Hz
Max.: Determined by
d1-02
Frequency
Command Lower
Limit
Sets the lower limit as a percentage of the
maximum output frequency
Default: 0.0 Hz
Min.: 0.0 Hz
Max.: Determined by
d1-02
Sets the Jump frequency range to avoid operation
at the speed causing resonance in the machinery.
Set L3-00 to L3-03 to 0.0 Hz to disable Jump
frequency.
When setting more than 1 Jump frequency, follow
the condition below.
L3-00 ≦ L3-01 ≦ L3-02
The maximum value
setting range is in
accordance with L2-01.
According to L2-01, the
maximum frequency
can be set to 110% of
d1-02. The L3 series is
set according to L2-01.
Sets the Jump frequency range to avoid.
Default: 1.00 Hz
Min.: 0.00 Hz
Max.: 20.00 Hz
L4: Frequency Command Hold and Up/Down 2 Command
Determines whether or not to save the frequency
command or the frequency bias (Up/Down 2)
value when the Stop command is entered or the
power supply is shut off.
0 ∶ Clear the Up/Down frequency at stop
1 ∶ Save the Up/Down frequency at stop
Default: 0
Range: 0, 1, 2